| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-03-024-004 as shown on this page.
A fixed-tubesheet bundle gives this configuration the thermal and mechanical margin expected of CHX compact equipment in compact liquid cooling. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. Its envelope centers on a 3-inch diameter shell, 24-inch shell length, and roughly 27-1/2 inches overall in a 2-pass arrangement. That works out to about 7.4 square feet of heat transfer surface on 5/8-inch O.D. tubes. That combination is cataloged as 5-030-03-024-004. As furnished, materials include cast iron bonnets, brass shell, copper tubes, and brass tubesheets. The unit is rated for 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature.