| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-02-008-002 as shown on this page.
For compact liquid cooling, the CHX compact line offers a fixed-tubesheet bundle design; this configuration sits within that range. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. The configuration measures 2 inches across the shell, 8-inch shell length, and roughly 11 inches overall in a 1-pass arrangement. That works out to about 1.2 square feet of heat transfer surface on 5/8-inch O.D. tubes. That combination is cataloged as 5-030-02-008-002. Material selection covers cast iron bonnets, brass shell, copper tubes, and brass tubesheets. Design ratings run to 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Typical duty includes hydraulic and lube oil cooling, injection molding machine cooling, and engine jacket water cooling.